韩国精品视频在线日韩,亚洲二区中文字幕在线,国产成人亚洲综合a∨婷婷,中文字幕成人电影,无码网,亚洲国产av剧一区二区三区,黑人又大又粗又硬XXXXX,欧美久久综合

    common problem

    Mechanical Damage Caused by Mechanical Turning of Cables

    author:admintime:2019-09-22 22:11click:
            Due to the large external diameter of mechanical power cables, it is difficult to transport and lay them, and the requirement for turning radius of power cables is stricter. In the construction of power cable, if the turning angle is too large, it may cause mechanical damage inside the conductor, and the mechanical damage will be reduced by the insulation strength of the cable until the failure occurs. A cable head fault is found in the construction. When the cable head is made, the length of the three cable heads is the same, and the connection with the equipment is limited by the terrain. The middle-phase cable head grows into an arch and discharges at the root of the cable head. After that, measures should be taken to shorten the connection length of the middle-phase cable head properly so that the three-phase cable head can not be subjected to external forces. Practice has proved that the operation effect is good. It can be seen that in the process of cable construction, the torsion of the cable should be reduced as much as possible. When the cable is turning and remaining, the cable should be in natural bending and the phenomenon of internal mechanical damage should be eliminated.